Vaillant Turbomax 242/282 1E Fault codes & diagnostics

121 fault codes with plain-English explanations, severity ratings, DIY guidance, and repair cost estimates.

Combi Natural Gas 24-28 kW 1998-2002 Discontinued

Replaced by: Turbomax Plus

Download the Vaillant Turbomax 242/282 1E manual The official installation & service manual (PDF) — the exact document these fault codes were verified against. PDF

This boiler uses indicator light combinations

Note which lights are on, off, or flashing and at what speed. Match the combination to the cards below. Do not reset until you have noted the pattern. How to read fault codes →

Severity at a glance

Each cell = one fault code. Hover to identify.
4 Emergency 98 High 13 Medium 6 Low

All 121 documented codes

Tap any card for details

Burner lock out indicator

Your boiler has stopped trying to light because it cannot detect a steady gas supply.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Printed Circuit Board
F.000

Your boiler has lost its connection to a temperature probe, meaning it can no longer accurately monitor how hot the water is, so it has safely shut itself down to prevent overheating.

High Engineer only £120-200 Shared across the range

Parts commonly replaced

  • NTC flow temperature sensor
  • Wiring harness / Cable loom
F.001

Your boiler has lost the connection to a temperature probe, so it cannot currently monitor your heating system effectively and has shut down as a precaution.

High Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Return NTC sensor
  • Wiring harness
F.002

Your boiler is struggling to detect the temperature of the water being heated for your taps, which means it has stopped providing hot water to be safe.

High Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Domestic hot water NTC sensor
  • Wiring harness / connection cable
F.003

Your boiler has lost the connection to the sensor that monitors your hot water tank temperature, meaning it doesn't know how hot the water currently is.

Medium Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Cylinder NTC sensor
  • Wiring harness

Related codes

F.010

Your boiler has stopped working because it is unable to accurately measure the temperature of the water inside the system due to a faulty electrical sensor connection.

High Engineer only £120-200 Shared across the range

Parts commonly replaced

  • NTC Flow Temperature Sensor
  • Wiring harness

Related codes

F.011

Your boiler has stopped working because one of its internal temperature sensors is giving a faulty electronic signal.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Return temperature sensor
  • Wiring harness

Related codes

F.012

Your boiler has detected an electrical fault with the sensor responsible for monitoring the temperature of your hot water, which prevents it from heating your taps correctly.

Medium Engineer only £120-200 Shared across the range

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring harness
F.013

Your boiler has lost the ability to accurately measure the temperature of your hot water cylinder because of a faulty electrical connection or sensor.

Medium Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Domestic Hot Water (DHW) cylinder sensor
  • Wiring harness

Related codes

F.020

Your boiler has automatically shut down because it detected that the internal water temperature has become dangerously high.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • NTC temperature sensor
  • Printed Circuit Board (PCB)
  • Pump

Related codes

Showing 11–20 of 121
F.022

Your boiler has stopped because the water pressure inside your heating system has dropped too low to operate safely.

High DIY-safe £0-£80 Shared across the range

What to check first

  1. Locate the external filling loop, which is usually a flexible silver braided hose with one or two valves located underneath your boiler.
  2. Slowly open the valve(s) to allow mains water into the system until the pressure gauge on the front of the boiler reads between 1.0 and 1.5 bar.
  3. Close the valve(s) tightly to ensure no water continues to leak into the system.

Parts commonly replaced

  • Pressure relief valve
  • Pressure sensor
  • Expansion vessel
F.023

Your boiler has detected that the water inside is not circulating properly, causing the temperature to rise much faster than it can be moved around your home.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Diverter valve
  • System filter

Related codes

F.024

Your boiler is shutting down because the water inside is heating up much faster than the system can pump it away, which often indicates poor circulation.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Central heating pump
  • System filter
  • Heat exchanger
F.025

Your boiler has detected that the exhaust gases leaving the flue are hotter than they should be, meaning the system is overheating and has shut down for safety.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • NTC temperature sensor
  • Heat exchanger
  • Pump
F.027

Your boiler has detected a flame even though it is not supposed to be running, which is a safety lockout to prevent potential hazards.

Emergency Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Gas valve
  • Printed Circuit Board (PCB)
  • Wiring harness
F.028

Your boiler is struggling because the pipe that carries away waste water is blocked, preventing the system from clearing itself safely.

High Engineer only £90-180 Shared across the range

Parts commonly replaced

  • Condensate trap
  • Condensate pipework
  • Siphon
F.029

Your boiler is unable to drain the water it produces during normal operation, which is causing it to automatically shut down for safety.

High Engineer only £90-180 Shared across the range

Parts commonly replaced

  • Condensate trap
  • Condensate pipework
  • Siphon
F.032

Your boiler is struggling to push air through the system correctly, which is stopping it from igniting safely.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Fan assembly
  • Hall sensor
  • PCB
F.035

Your boiler is struggling to breathe because the pipe that vents exhaust gases outside is obstructed or blocked, preventing it from operating safely.

Emergency Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Fan
  • Air pressure switch
  • Flue terminal
F.040

Your boiler is struggling to get the right balance of air and fuel to burn properly, so it has turned itself off to stay safe.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Gas valve
  • Flue seal
  • Air pressure switch
  • Venturi
Showing 21–30 of 121
F.042

Your boiler's electronic brain is unable to identify essential settings because a small plug-in component responsible for defining the boiler's configuration has become faulty or loose.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Coding resistor
  • Main printed circuit board (PCB)

Related codes

F.044

Your boiler is failing to detect a flame, which means it cannot safely light to provide you with heating or hot water.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Ignition electrode
  • Ionisation probe
  • PCB
F.047

Your boiler is confused because it is receiving an illogical temperature reading from the sensor that monitors your hot water supply.

Medium Engineer only £120-220 Shared across the range

Parts commonly replaced

  • NTC sensor
  • Wiring harness

Related codes

F.049

Your boiler's internal communication system is experiencing a wiring conflict or short-circuit, preventing it from sending signals to the main controls.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • eBUS connection wiring
  • Printed Circuit Board (PCB)
F.057

Your boiler has detected a failure in its internal safety systems responsible for managing the gas and air mixture, and it has shut down completely to prevent unsafe operation.

Emergency Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Gas valve
  • PCB (Printed Circuit Board)
  • Flue gas analysis sensor
F.061

Your boiler's internal computer is failing to start up or communicate correctly, which prevents it from operating safely.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Main PCB
  • Wiring harness
F.062

Your boiler's internal sensor has detected that the flame is not turning off as quickly as it should once the heating or hot water cycle has finished.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Gas valve
  • Printed circuit board (PCB)

Related codes

F.063

Your boiler’s internal computer is experiencing a memory error, meaning it can no longer remember or process its programmed start-up instructions correctly.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Main Printed Circuit Board (PCB)

Related codes

F.064

Your boiler's electronic brain has developed an internal error and can no longer safely control the heating or hot water system.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)

Related codes

F.065

Your boiler has detected that an internal electronic component is overheating, so it has safely shut itself down to prevent damage.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • NTC thermistor
Showing 31–40 of 121
F.067

Your boiler is unable to safely detect the flame, so it has shut itself down to prevent a gas leak.

Emergency Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Flame detection probe
F.068

Your boiler is struggling to keep a steady flame, causing it to shut down for safety reasons.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Flame rectification electrode
  • Ignition lead
  • Printed Circuit Board (PCB)
F.070

Your boiler's computer has lost track of its specific identification settings, meaning it cannot properly manage its internal operations to heat your home.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Main electronic control board (PCB)
  • Coding resistor

Related codes

F.071

Your boiler has stopped working because it is unable to accurately measure the temperature of the water inside the unit, so it has shut down as a precaution.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • NTC flow temperature sensor
  • Wiring harness

Related codes

F.072

Your boiler has detected an inconsistent temperature difference between the water leaving and returning to the system, causing it to stop heating as a precaution.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Flow NTC sensor
  • Return NTC sensor
  • Printed Circuit Board (PCB)

Related codes

F.074

Your boiler has lost the connection to the sensor that measures how much water is circulating inside, meaning it cannot safely confirm there is enough pressure to operate.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness
F.075

Your boiler is struggling because it cannot detect enough water movement when the pump turns on, causing it to block its own operation to prevent damage.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Flow sensor
  • Printed circuit board

Related codes

F.076

Your boiler has detected that the internal components are getting too hot and has automatically shut down to prevent damage.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • NTC temperature sensor
  • Central heating pump
  • Primary heat exchanger
F.077

Your boiler has detected an issue with the drainage system or flue venting, which is preventing it from safely lighting the burner.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Condensate pump
  • Flue non-return flap
  • PCB

Related codes

F.078

Your boiler's computer system is having trouble recognising a control component, meaning it cannot safely manage your heating and hot water.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Main printed circuit board (PCB)
  • Control unit interface

Related codes

Showing 41–50 of 121
F.080

Your boiler is struggling to accurately measure the incoming cold water temperature, which may cause your hot water to run inconsistently or at the wrong temperature.

Medium Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Cold water NTC thermistor
  • Wiring harness
F.081

Your boiler is struggling to heat the water in your separate hot water cylinder, meaning you may not have any hot water available.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Diverter valve
  • NTC sensor
  • Pump
F.083

Your boiler is failing to heat up because it cannot detect a rise in temperature after the flame ignites, which usually means the water isn't circulating properly.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Pump
  • Diverter valve
  • NTC sensor
F.084

Your boiler is confused because the water temperature readings coming from different parts of the system do not match up properly.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • NTC flow sensor
  • NTC return sensor
  • PCB

Related codes

F.085

Your boiler has detected that the internal temperature sensors are not positioned correctly, preventing it from heating your home safely.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • NTC Temperature Sensor
  • Sensor Wiring Harness

Related codes

F.087

Your boiler has lost the internal electrical connection needed to create the spark that lights the flame.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Ignition lead
  • Ignition transformer
  • PCB
F.088

Your boiler has lost the electrical signal required to open the gas supply, meaning it cannot ignite to produce heat or hot water.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Gas valve wiring harness
  • Gas valve assembly
  • Printed Circuit Board (PCB)
F.089

Your boiler's computer has detected that the water pump inside does not match the specifications required for this older model, preventing the system from circulating heat effectively.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Printed Circuit Board (PCB)

Related codes

F.090

Your boiler has lost the electronic connection needed to communicate with your hot water storage device.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • PCB
  • Wiring harness
  • Connection cable

Related codes

F.092

Your boiler has detected that it hasn't been correctly set up for the specific type of gas currently being supplied to your home, which prevents it from firing safely.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Gas valve
  • PCB (Printed Circuit Board)
Showing 51–60 of 121
F.095

Your boiler is struggling to correctly control the amount of gas entering the burner, meaning it cannot maintain a flame.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve
  • PCB
F.096

Your boiler has detected that the internal mechanism controlling your gas flow is struggling to operate correctly, causing it to stop for safety reasons.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve stepper motor
  • Gas valve assembly
  • PCB
F.097

Your boiler's computer has detected an internal error and cannot safely start up, meaning you currently have no heating or hot water.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Main PCB (Printed Circuit Board)
F.105

Your boiler is struggling to communicate with its internal fuel regulation system, meaning it cannot safely ignite to provide heating or hot water.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve
  • Printed Circuit Board (PCB)
F.194

Your boiler's main control unit has developed an internal electrical fault and is unable to communicate with its power supply.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Control unit
F.195

Your boiler has detected that the incoming electricity supply is too weak or unstable to operate safely.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Main PCB
  • Wiring harness
F.196

Your boiler has detected that the incoming electricity supply is at a dangerously high voltage, causing the system to shut down to prevent internal electrical damage.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Main Electronic PCB
  • Surge Protection Device
F.317

Your boiler is struggling to detect if you are running the hot tap, which means it may fail to heat your water properly.

Medium Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Flow sensor
  • Wiring harness
F.318

Your boiler is struggling to switch between heating your radiators and heating your hot water because a mechanical valve responsible for directing the water flow has become stuck.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • 3-port motorised valve actuator
  • 3-port valve mid-position unit
F.320

Your boiler's water pump is stuck, meaning it cannot circulate heat around your home to warm your radiators or taps.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Pump capacitor
Showing 61–70 of 121
F.321

Your boiler's water circulation pump has developed an internal electrical fault, meaning it cannot move heat around your home.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Circulation pump
  • Pump wiring harness
F.322

Your boiler has detected that the internal water pump is running too hot and cannot cool down, causing it to shut off for safety to prevent further damage.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Printed Circuit Board (PCB)
F.323

Your boiler has detected that the water pump is struggling to move water around the system, possibly due to air being trapped inside.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Circulation pump
  • Pressure sensor
F.324

Your boiler is unable to move water around because the internal pump has lost its electrical power connection, meaning your heating and hot water will not work.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Wiring harness
  • Main PCB
F.325

Your boiler is unable to move water through the system because the internal pump, which acts as the heart of your heating, has stopped working correctly.

High Engineer only £200-350 Shared across the range

Parts commonly replaced

  • Circulation pump
  • Pump head
  • Printed Circuit Board (PCB)
F.326

Your boiler has detected that several internal mechanical parts are failing to move correctly, meaning it has shut down to prevent further damage.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Diverter valve actuator
  • Main PCB
  • Pump
F.327

Your boiler is confused because it thinks it shouldn't be heating water for your taps, which is preventing it from running your heating normally.

Medium Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Diverter valve
  • Main PCB
  • Flow sensor
F.330

Your boiler has detected that the internal water pump is not spinning as it should, so it has shut down to prevent the system from overheating.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Printed Circuit Board (PCB)
  • Wiring harness
F.334

Your boiler is confused because it hasn't been properly programmed to recognise the pipework that vents your exhaust gases.

High Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Main PCB
F.336

Your boiler's electronic control system has detected a mismatched or incorrect setting that prevents it from operating safely.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Coding resistor plug
Showing 71–80 of 121
F.337

Your boiler has detected that the flue system installed is incompatible with the boiler's internal components, which can prevent safe operation.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Flue adaptor
  • PCB
F.338

Your boiler has detected that the settings controlling how it vents exhaust gases do not match how it was actually installed.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Main printed circuit board (PCB)
  • Flue sensor
F.342

Your boiler is struggling to breathe properly because the airflow inside the unit is blocked or the internal fan isn't moving enough air.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Flue system components
F.343

Your boiler's air-flow monitoring system is struggling to read data correctly, which prevents it from safely igniting.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Air pressure switch
  • Flue fan
  • PCB
F.344

Your boiler has detected an issue with the sensor responsible for monitoring the flame, meaning it cannot safely ignite or stay running.

High Engineer only £180-300 Shared across the range

Parts commonly replaced

  • Control board
  • Ignition lead
  • Electrode assembly
F.347

Your boiler has detected that waste water cannot drain away properly, which is stopping it from working to protect the internal parts.

High Engineer only £90-160 Shared across the range

Parts commonly replaced

  • Condensate siphon
  • Condensate trap
  • External discharge pipe
F.363

Your boiler's computer memory is experiencing internal data errors, meaning the device cannot properly save or recall its operating settings.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Main electronic PCB
  • Control board
F.707

Your boiler's electronic control panel and internal computer are failing to talk to each other, meaning the unit cannot receive instructions to provide heating or hot water.

High Engineer only £200-450 Shared across the range

Parts commonly replaced

  • User interface/display unit
  • Main printed circuit board (PCB)
  • Communication cable/ribbon harness
F.905

Your boiler's internal parts are having a communication failure, likely due to an electrical surge or short circuit, which is preventing it from running.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Wiring harness
L.016

Your boiler has shut down because the flame went out unexpectedly while it was running at its lowest power setting.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Flame sensing electrode
  • Gas valve
  • Printed Circuit Board (PCB)
Showing 81–90 of 121
L.022

Your boiler has detected that there is not enough water pressure circulating through your heating system to operate safely.

High DIY-safe £80-150 Shared across the range

What to check first

  1. Locate the filling loop, which is a silver braided hose with one or two valves located underneath the boiler.
  2. Open the valve(s) slowly to allow mains water into the system until the pressure gauge on the front of the boiler reads between 1.0 and 1.5 bar.
  3. Close the valve(s) firmly and ensure no water is leaking from the connection.

Parts commonly replaced

  • Filling loop
  • Pressure gauge
  • Central heating pump
L.025

Your boiler is struggling to accurately measure the temperature of the water coming into the system from the mains, which may interfere with your hot water control.

Low Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Cold water inlet NTC sensor
  • Wiring harness
L.032

Your boiler is struggling to detect the flow of water through the system, which means it cannot safely provide heating or hot water.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Flow sensor
  • Wiring harness
L.095

Your boiler's gas control mechanism is struggling to adjust, which means it cannot regulate the flame correctly and will stop heating water to stay safe.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve
  • PCB
L.096

Your boiler's gas valve is struggling to adjust properly, meaning the device cannot safely ignite or maintain its fire to heat your home.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve stepper motor
  • Gas valve assembly
  • Main PCB
L.097

Your boiler is struggling to mix the right amount of air with the gas needed for safe combustion, which has caused it to stop working to protect your home.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Gas valve
  • Venturi
  • Fan assembly
L.105

Your boiler is struggling to remove trapped air from its system, which is preventing it from starting up correctly.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Automatic Air Vent
  • Circulation Pump
L.144

Your boiler is struggling to detect the flame needed to heat your water and home, so it has shut down to stay safe.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Ionisation electrode
  • Ignition lead
  • PCB
L.194

Your boiler's internal computer is not receiving stable power, causing it to shut down to prevent further damage.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Power Supply Module
L.195

Your boiler is struggling because the electricity coming into it from your home's mains supply is too weak or unstable.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Electrical wiring harness
Showing 91–100 of 121
L.196

Your boiler has detected that the incoming electricity supply is at a dangerously high voltage, causing it to shut down to protect its internal electronics.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Main PCB
  • Surge protection fuse
L.319

Your boiler is struggling to push water around your heating system because a small internal safety valve is stuck, which may cause it to turn itself off to prevent overheating.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Bypass valve
  • Diverter valve cartridge
L.320

Your boiler's water pump is stuck, so it is currently unable to circulate heat around your home.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Pump head
L.322

Your boiler has detected that the water pump is running too hot and has stopped working to prevent further damage.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Circulation pump
  • Pump wiring harness
  • Printed Circuit Board (PCB)
L.343

Your boiler is struggling to accurately measure the airflow needed for safe combustion, so it has safely shut itself down to prevent any issues.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Air pressure switch
  • Venturi
  • Fan assembly
  • Wiring harness
N.013

Your boiler is struggling to read its internal water pressure, which prevents it from safely igniting and providing you with heating or hot water.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness
  • Printed Circuit Board
N.027

Your boiler is struggling to accurately measure the temperature of the hot water it is producing, so it has safely paused to prevent overheating.

Medium Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Domestic hot water NTC sensor
  • Wiring harness
N.032

Your boiler is struggling to detect how much water is flowing through the system, which currently prevents it from heating your water correctly.

High Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Hall effect flow sensor
  • Wiring harness
N.089

The boiler is detecting that a replacement part fitted to the internal water circulating system is not compatible with your specific model.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Circulation pump
  • PCB
N.095

Your boiler's gas control mechanism is struggling to regulate the fuel supply properly, which is preventing the burner from igniting reliably.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve stepper motor
  • Gas valve assembly
Showing 101–110 of 121
N.096

Your boiler's gas control mechanism has reached its operational limit and can no longer adjust the flame correctly, causing the boiler to stop working.

High Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Gas valve stepper motor
  • Gas valve assembly
N.097

Your boiler is struggling to mix the right amount of air with the gas needed for combustion, which means it will likely shut down to prevent inefficient burning.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Venturi
  • Gas valve
  • Fan assembly
  • Air pressure switch
N.100

Your boiler has lost the connection to the external sensor that tells it how cold it is outside, so it is defaulting to a standard internal setting.

Low Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Outdoor temperature sensor
  • Wiring harness
N.144

Your boiler is failing to detect the flame correctly, so it has safely shut itself down to prevent gas from building up.

High Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Flame rectification electrode
  • Ignition lead
  • PCB
N.194

Your boiler's internal electrical control system has failed, preventing it from starting up or operating your heating and hot water.

High Engineer only £250-450 Shared across the range

Parts commonly replaced

  • Main PCB
  • Power supply module
N.270

Your boiler is struggling to manage the temperature difference between your heating and hot water systems, so it has slowed down its performance to prevent overheating.

High Engineer only £150-350 Shared across the range

Parts commonly replaced

  • Diverter valve
  • Plate-to-plate heat exchanger
  • NTC thermistor sensor
N.317

Your boiler is struggling to detect the flow of water when you turn on a hot tap, meaning it doesn't know you need hot water.

Medium Engineer only £150-250 Shared across the range

Parts commonly replaced

  • Turbine / Hall effect sensor
  • Wiring harness
N.319

Your boiler is struggling to push water around your heating system because a small internal pathway meant to balance pressure is blocked.

Medium Engineer only £180-350 Shared across the range

Parts commonly replaced

  • Bypass valve cartridge
  • Diverter valve assembly
N.324

Your boiler has lost the electrical signal to the pump responsible for moving water around your heating system, so it has safely shut down to prevent overheating.

High Engineer only £120-220 Shared across the range

Parts commonly replaced

  • Central heating pump
  • Wiring harness
  • Printed Circuit Board (PCB)
N.343

Your boiler is struggling to accurately measure the airflow needed for combustion, so it has entered a restricted mode to keep running safely.

Medium Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Air pressure switch
  • Venturi nozzle
  • Fan assembly
  • Wiring harness
Showing 111–120 of 121
S.032

Your boiler has detected that the air circulation fan is struggling to maintain a steady speed and has automatically tried to restart itself to correct the issue.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Fan assembly
  • Hall sensor
  • PCB
S.041

Your boiler has detected that the water pressure in your heating system is currently too high for safe and efficient operation.

Medium DIY-safe £80-150 Shared across the range

What to check first

  1. Locate a radiator in your home with a bleed valve.
  2. Use a radiator key to slightly open the valve and release some water into a container.
  3. Monitor the pressure gauge on your boiler until it drops to the recommended range of 1.0 to 1.5 bar.

Parts commonly replaced

  • Pressure relief valve
  • Expansion vessel
  • Pressure sensor

Related codes

S.042

Your boiler is temporarily pausing its operation because an external add-on, like a drainage pump or flue safety flap, is signaling that it is not ready for the boiler to fire up.

Medium Engineer only £120-250 Shared across the range

Parts commonly replaced

  • Condensate pump
  • Flue non-return flap
  • External wiring loom
S.054

Your boiler has detected low water pressure and is currently sitting in a waiting period to protect itself from damage.

High DIY-safe £80-150 Shared across the range

What to check first

  1. Locate the external filling loop (a flexible silver hose) beneath the boiler.
  2. Open the filling valve slowly until the pressure gauge reads between 1.0 and 1.5 bar.
  3. Close the valve tightly and check for any leaks.

Parts commonly replaced

  • Pressure sensor
  • Filling loop
  • Pressure gauge
S.057

Your boiler has detected an issue with the combustion process and has temporarily paused itself to ensure safety before attempting to restart.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Air pressure switch
  • Flue fan
  • Gas valve
S.059

Your boiler is preventing itself from firing up because it cannot detect enough water flowing through the system to heat your home safely.

High DIY-safe £120-250 Shared across the range

What to check first

  1. Check that all your radiator valves are fully open
  2. Ensure your system pressure is at the recommended level (usually 1.0 to 1.5 bar) using the filling loop
  3. Check that any external zone valves or system bypass valves are not stuck or obstructing flow

Parts commonly replaced

  • Central heating pump
  • Flow sensor
  • System bypass valve
S.096

Your boiler is currently running an automatic internal safety check on its temperature sensors and has temporarily paused heating until this process finishes.

Low Engineer only £120-200 Shared across the range

Parts commonly replaced

  • Return temperature sensor
  • Wiring harness
S.097

Your boiler is currently running a routine internal check on its water pressure sensors and has temporarily paused heating to complete the scan.

Low Engineer only Shared across the range

Parts commonly replaced

  • Water pressure sensor
  • Main printed circuit board (PCB)
S.098

Your boiler is currently running an automatic system check and has temporarily paused heating and hot water to ensure all safety measures are functioning correctly.

Low Engineer only £100-250 Shared across the range

Parts commonly replaced

  • NTC Temperature Sensor
  • PCB
Showing 121–121 of 121
S.599

Your boiler has detected an internal communication error and has locked itself out to prevent further damage.

High Engineer only £150-300 Shared across the range

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Wiring Harness

51 operating states & engineer diagnostics

Not faults — these are normal operating states. Tap to expand.

Fan operation indicator Status Your boiler is successfully checking that its internal air extraction system is working correctly, which is a normal part of the startup process. Flame indicator Status Your boiler is working exactly as it should and has successfully lit the flame to heat your water or home. Hot water demand indicator Status Your boiler is working exactly as it should and is simply confirming that it has received your request to heat water for your tap or shower. Ignition indicator Status Your boiler is attempting to light the flame, but it is not staying lit or detecting the burner, which prevents your heating and hot water from working. Power on indicator Status Your boiler is receiving power as normal and is currently switched on. I.003 Diagnostic Your boiler has reached its programmed service interval and is kindly reminding you that it is time for a routine professional safety check. I.020 Diagnostic Your boiler has detected that the water level in your heating system has dropped slightly below the recommended amount. I.144 Diagnostic Your boiler’s internal ignition sensor is reaching the end of its life and is struggling to accurately detect the burner flame. S.000 Status Your boiler is currently in standby mode because it is not receiving a signal from your thermostat or timer to turn on the heating. S.001 Status Your boiler is currently preparing to ignite and is simply checking that the internal exhaust fan is working correctly before starting the heating process. S.002 Status Your boiler is currently preparing to fire up and is performing a routine start-up check before the heating begins. S.003 Status Your boiler is operating normally and is currently firing up to provide your home with heating. S.004 Status Your boiler is operating normally and is currently heating your radiators. S.005 Status Your boiler is currently just finishing its normal internal cooling cycle after heating your home and does not have a fault. S.006 Status Your boiler is currently working normally and is simply running its fan to clear out any leftover gases after a heating cycle. S.007 Status Your boiler is currently transitioning between heating cycles and is simply moving leftover warm water through your radiators, which is a normal part of its cooling-down process. S.008 Status Your boiler is currently taking a short, intentional rest period between heating cycles to prevent excessive wear on the system. S.009 Status Your boiler is currently performing a routine, automatic internal maintenance check to ensure its ignition parts are working as efficiently as possible. S.010 Status Your boiler is currently in standby mode because it does not detect a request for hot water. S.011 Status Your boiler is currently working exactly as it should and is preparing to provide you with hot water. S.012 Status Your boiler is currently preparing to provide hot water, so this is a normal operational status message rather than a fault. S.013 Status This code simply indicates that your boiler is doing exactly what it's supposed to do by heating your water when you turn on a hot tap. S.014 Status Your boiler is currently working exactly as it should to provide you with hot water, so there is no need for concern. S.015 Status Your boiler is currently just finishing its standard cooldown process after you recently used your hot water taps. S.016 Status Your boiler is currently finishing its final safety cooling cycle after you have finished using hot water. S.017 Status Your boiler is currently running the internal pump after you have finished using hot water to ensure the system cools down safely; this is a normal operational status, not a fault. S.019 Status Your boiler is simply performing a routine, automatic internal health check while you are using hot water, and no action is required. S.020 Status Your boiler is currently working correctly; it is simply in standby mode because it has not been asked to heat your hot water tank or radiators. S.021 Status Your boiler is currently heating the water stored in your hot water cylinder, which is a normal part of its operational cycle. S.022 Status Your boiler is currently preparing to heat your hot water tank and is just waiting for the internal water pump to get up to speed. S.023 Status Your boiler is currently heating up the internal hot water store to ensure you have a ready supply of hot water. S.024 Status Your boiler is currently operating normally as it has successfully finished heating the water in your separate hot water tank. S.025 Status Your boiler is currently heating your hot water storage tank and is in the final stages of completing that process, so there is no need to worry. S.026 Status Your boiler is currently heating your hot water storage tank and running the fan to clear exhaust gases, which is a normal part of its operation. S.027 Status Your boiler is currently busy heating up your hot water storage tank, which is a normal part of its operation. S.028 Status Your boiler is currently waiting for a short period before it can restart to heat your water, which is a normal part of its internal safety cycle. S.029 Status Your boiler is currently performing a routine self-calibration process to ensure its flame sensor stays accurate, so you do not need to take any action. S.030 Status Your boiler is currently in standby mode because it is not receiving a signal from your thermostat to turn on the heating. S.031 Status Your boiler is currently idle because it has not been asked to provide any heating or hot water at this moment. S.034 Status Your boiler has detected that the temperature is low and is currently running its automatic internal protection cycle to prevent the pipes from freezing. S.039 Status Your boiler is currently indicating that it is not in a normal operating state because a specific internal sensor is detecting an issue with the sensor located at the base of the unit. S.088 Status Your boiler is currently performing a brief automatic air-clearing cycle, which is a normal process and does not indicate a fault. S.091 Status Your boiler is currently stuck in a demonstration or shop display mode, which prevents it from operating normally for heating or hot water. S.092 Status Your boiler is currently performing an automated internal health check to measure how well water is flowing through the system. S.093 Diagnostic Your boiler is currently unable to perform an internal check on its exhaust gases, meaning it has paused its operation to ensure it is running safely. S.109 Status Your boiler is currently in standby mode and is working exactly as it should. S.199 Status Your boiler has detected that it is currently topping itself up with fresh water automatically to maintain the correct pressure. S.326 Diagnostic Your boiler is currently performing a brief automatic self-check of its internal water valves and flow components. S.328 Status Your boiler is constantly running a secondary pump that is not actually part of the heating system, which is keeping the unit in a perpetual state of activity. S.335 Status Your boiler is pausing to perform a safety check to ensure that exhaust gases are not being blocked from exiting your home. S.341 Status Your boiler is simply taking a short break from running at full power because it has been heating your home for a long time.