Vaillant ecoFIT Pure 435 Fault codes & diagnostics

71 fault codes with plain-English explanations, severity ratings, DIY guidance, and repair cost estimates.

Regular Natural Gas 35 kW 2017-present
GC Number 41-694-19
Download the Vaillant ecoFIT Pure 435 manualThe official installation and service manual (PDF), the document these fault codes were read from. PDF
Other editions of this manual (the one above is 0020230535_09): 0020230535_01 (PDF) Manufacturers revise a model over the years. If your boiler is older than the manual above, an earlier edition may match it better.

The fault code is already on your display

Note it down before pressing reset — resetting clears the code immediately. How to read fault codes →

Severity at a glance

Each cell = one fault code. Hover to identify.
4 Emergency 37 High 4 Medium 26 Low

All 71 documented codes

Tap any card for details

con

Your boiler's display screen has lost its connection to the main computer inside, meaning it cannot control or run your heating system.

High Engineer only £150-350

Parts commonly replaced

  • User interface display
  • Main PCB
  • Connecting wiring harness

Related codes

F.00

Your boiler has lost its connection to the temperature sensor, meaning it no longer knows how hot the water is and has stopped working to keep you safe.

High Engineer only £120-220

Parts commonly replaced

  • Flow temperature sensor (NTC)
  • Wiring harness

Related codes

F.01

Your boiler has lost the connection to the sensor that monitors the temperature of the water returning to the unit, causing it to stop working for safety reasons.

High Engineer only £120-220

Parts commonly replaced

  • Return temperature sensor
  • Wiring harness

Related codes

F.10

Your boiler has stopped working because a sensor that measures water temperature is providing an incorrect signal, so the system has safely shut down to prevent overheating.

High Engineer only £120-220

Parts commonly replaced

  • NTC flow temperature sensor
  • Wiring harness

Related codes

F.11

Your boiler has detected a faulty signal from a heat sensor, causing it to shut down for safety to prevent overheating.

High Engineer only £120-220

Parts commonly replaced

  • Return NTC thermistor sensor
  • Wiring harness

Related codes

F.13

Your boiler has temporarily stopped working because it has detected a faulty reading from its internal temperature sensor.

High Engineer only £90-180

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring Harness

Related codes

F.22

Your boiler has automatically shut down because the internal water pressure has dropped too low to operate safely.

High DIY-safe

What to check first

  1. Locate the filling loop valves underneath your boiler or near your hot water cylinder.
  2. Open the valves slowly to let mains water into the system until the pressure gauge reads between 1.0 and 1.5 bar.
  3. Close both valves tightly and reset the boiler using the reset button.

Parts commonly replaced

  • Pressure relief valve
  • Expansion vessel
  • Pressure sensor

Related codes

F.23

Your boiler has shut itself down because the water inside is getting too hot too quickly, usually due to a blockage or a stuck valve.

High Engineer only £150-350

Parts commonly replaced

  • Water pump
  • Flow sensor
  • Motorised valve

Related codes

F.24

Your boiler is temporarily shutting down because the water inside is heating up much faster than normal, usually due to poor water flow.

High Engineer only £150-300

Parts commonly replaced

  • Pump
  • Heat exchanger
  • NTC thermistor

Related codes

F.25

Your boiler has automatically shut down because the exhaust gases are getting too hot, or a safety connection linked to the flue has come loose.

Emergency Engineer only £100-£250

Parts commonly replaced

  • Flue gas safety cut-out (SCO)
  • Cable harness

Related codes

Showing 11–20 of 71
F.27

Your boiler has temporarily locked out because it falsely detects a flame inside when it shouldn't be there, usually due to moisture on the internal electronics or a faulty valve.

Emergency Engineer only £150-350

Parts commonly replaced

  • Main PCB
  • Gas valve

Related codes

F.28

Your boiler is trying to start up, but it cannot detect a successful flame to get the heating or hot water going.

High Engineer only £150-300

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • PCB

Related codes

F.29

Your boiler tried to fire up several times but couldn't keep the flame going, so it has safely shut itself down.

High Engineer only £120-250

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Ignition transformer
  • Condensate trap

Related codes

F.32

Your boiler has stopped working because it cannot detect that its internal fan is spinning properly to safely clear exhaust gases.

High Engineer only £150-300

Parts commonly replaced

  • Fan
  • Wiring harness
  • Main PCB

Related codes

F.49

Your boiler has detected an electrical communication problem in its internal wiring control system, causing it to shut down to protect its internal electronics.

High Engineer only £100-£250

Parts commonly replaced

  • Main Printed Circuit Board (PCB)
  • Wiring harness

Related codes

F.61

Your boiler has detected an electrical fault with the gas valve, meaning it cannot safely open to let gas through for heating and hot water.

High Engineer only £150-300

Parts commonly replaced

  • Gas valve assembly
  • Wiring harness
  • Main PCB

Related codes

F.62

Your boiler has detected an issue with the gas valve not shutting off properly, which means a qualified engineer must inspect it immediately for safety.

Emergency Engineer only £200-400

Parts commonly replaced

  • Gas valve
  • Main PCB

Related codes

F.63

Your boiler's main computer control panel has suffered a critical internal memory failure and can no longer process instructions to run your heating system.

High Engineer only £250-450

Parts commonly replaced

  • Main PCB (Printed Circuit Board)

Related codes

F.64

Your boiler has detected a sudden reading error with its internal temperature sensors or main control board, causing it to lock out for safety.

High Engineer only £150-350

Parts commonly replaced

  • Flow NTC sensor
  • Return NTC sensor
  • Main printed circuit board (PCB)

Related codes

F.65

Your boiler has detected that its internal computer is running too hot and has safely shut down to prevent permanent damage.

High Engineer only £150-350

Parts commonly replaced

  • Main PCB
  • Electronics housing
  • Cooling fan

Related codes

Showing 21–30 of 71
F.67

Your boiler has temporarily stopped working because the internal computer is receiving a confusing signal from the flame sensor.

High Engineer only £150-£400

Parts commonly replaced

  • Main PCB (Circuit Board)
  • Flame sensor electrode

Related codes

F.68

Your boiler is safely shutting down because the burner flame is flickering or going out unexpectedly, which can be caused by gas supply issues or a blocked exhaust.

Emergency Engineer only £100-250

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Condensate trap

Related codes

F.70

Your boiler's main computer is experiencing an identity crisis because a replacement part was recently installed without being programmed correctly to match your specific model.

High Engineer only £90-150

Parts commonly replaced

  • Coding Resistor
  • Printed Circuit Board (PCB)

Related codes

F.71

Your boiler has temporarily stopped working because a sensor measuring the water temperature is giving a constant or incorrect reading.

High Engineer only £90-£180

Parts commonly replaced

  • Flow temperature sensor
  • Sensor retaining clip/spring

Related codes

F.72

Your boiler has temporarily stopped working because it has detected a disagreement between its temperature sensors, meaning it cannot safely measure how hot the water is.

High Engineer only £120-250

Parts commonly replaced

  • Flow temperature sensor
  • Return temperature sensor
  • NTC sensor harness

Related codes

F.73

Your boiler is not receiving a proper signal from its water pressure sensor, meaning it cannot accurately check the water level inside the system.

High Engineer only £90-180

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

F.74

Your boiler has detected an electrical fault with the internal water pressure sensor, which is reading a pressure signal that is too high.

Medium Engineer only £120-250

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

F.75

Your boiler has detected that the water pressure isn't rising correctly when the internal pump starts up, which usually points to low system pressure, trapped air, or a faulty sensor.

High DIY-safe £90-£250

What to check first

  1. Check the system pressure gauge on the front of the boiler to see if it is below 1 bar.
  2. Use the filling loop underneath the boiler to top up the pressure to between 1 and 1.5 bars.
  3. Restart or reset the boiler to clear the fault code.

Parts commonly replaced

  • Water pressure sensor
  • Central heating pump
  • Automatic air vent

Related codes

F.76

Your boiler has automatically shut down because a safety device detected that the main part of the boiler has become dangerously hot.

High Engineer only £150-350

Parts commonly replaced

  • Primary heat exchanger safety fuse
  • Wiring harness
  • Primary heat exchanger

Related codes

F.77

Your boiler has detected an issue with the system that removes waste water or controls the exhaust gases, causing it to lock out for safety.

High Engineer only £150-300

Parts commonly replaced

  • Condensate pump
  • Flue non-return flap
  • Printed Circuit Board (PCB)

Related codes

Showing 31–40 of 71
F.83

Your boiler has detected that the water inside is not heating up or moving properly right after it turns on.

High Engineer only £120-250

Parts commonly replaced

  • NTC Temperature Sensor
  • Flow and Return Sensors

Related codes

F.84

Your boiler has detected that the temperature sensors measuring how water enters and leaves the system are giving contradictory or reversed readings.

High Engineer only £100-250

Parts commonly replaced

  • Flow temperature sensor
  • Return temperature sensor
  • Wiring harness

Related codes

F.85

Your boiler's temperature sensors have been attached to the wrong pipes during installation, meaning it cannot properly measure how water flows through the system.

Medium Engineer only £90-180

Parts commonly replaced

  • Flow temperature sensor
  • Return temperature sensor
  • Wiring harness

Related codes

F.87

Your boiler has lost its electrical connection to the part that creates the ignition spark, meaning it cannot safely light to provide heating or hot water.

High Engineer only £90-180

Parts commonly replaced

  • Wiring harness
  • Main PCB

Related codes

F.88

Your boiler has lost its electrical connection to the gas valve, meaning it cannot safely let gas through to heat your home.

High Engineer only £90-180

Parts commonly replaced

  • Gas valve wiring harness
  • PCB

Related codes

F.89

Your boiler has detected an issue with the internal water pump's connection or electronic signals, causing it to shut down for safety.

High Engineer only £150-300

Parts commonly replaced

  • Internal water pump
  • Wiring harness
  • Main PCB

Related codes

F.97

Your boiler's internal computer has failed a self-test and is no longer able to communicate with the rest of the system.

High Engineer only £300-£550

Parts commonly replaced

  • Main PCB (Printed Circuit Board)

Related codes

S.0

Your boiler is currently in standby mode because it has not been asked to provide any heating or hot water at this moment.

Low DIY-safe

What to check first

  1. Check your room thermostat or smart controller settings to ensure a temperature demand is set
  2. Ensure your heating timer or schedule is currently set to 'ON'
  3. Check that you have a demand for hot water by opening a tap

Related codes

S.02

Your boiler is simply getting ready to start the heating by running the internal water pump for a few moments, which is a normal part of its startup routine.

Low Engineer only
Showing 41–50 of 71
S.05

Your boiler is currently cooling itself down by circulating water and venting air, which is a normal part of the shutdown process after your heating has been running.

Low Engineer only
S.08

Your boiler is simply taking a short, scheduled rest period after completing a heating cycle to allow the water temperature to balance.

Low Engineer only
Showing 51–60 of 71
S.25

Your boiler is currently just finishing a routine cooling-down process after providing hot water and should return to normal operation shortly.

Low Engineer only
S.26

Your boiler's fan is attempting to spin, but the electronic control board isn't receiving the correct signal back to confirm it is working properly.

High Engineer only £250-550

Parts commonly replaced

  • Fan assembly
  • Main PCB
  • Wiring harness

Related codes

S.27

Your boiler is simply finishing its cooling cycle after providing hot water and is operating exactly as it should.

Low Engineer only
S.28

Your boiler has temporarily paused heating your hot water to let things cool down or adjust, which is a normal safety feature rather than a breakdown.

Low Engineer only
S.30

Your boiler is working perfectly, but it is currently being told to stay off by your room thermostat or smart home control system.

Low DIY-safe

What to check first

  1. Check your room thermostat or smart heating app to ensure the target temperature is set higher than the current room temperature.
  2. Replace the batteries in your room thermostat if they are low.
  3. Check that your heating schedule is set to 'On' and not currently in an 'Off' or 'Away' period.

Parts commonly replaced

  • External thermostat
  • Smart heating receiver

Related codes

S.31

Your boiler is currently in summer mode or waiting for a heating signal from your thermostat, which is a normal standby state rather than a fault.

Low DIY-safe

What to check first

  1. Check your room thermostat or heating programmer to ensure a heating temperature is requested.
  2. Verify that your heating is not switched off or set to summer mode on the boiler control panel.

Related codes

S.32

Your boiler is pausing because its internal air-flow system is not operating at the correct speed to run safely.

High Engineer only £180-350

Parts commonly replaced

  • Fan assembly
  • Printed Circuit Board (PCB)
  • Wiring harness

Related codes

S.34

Your boiler is temporarily running its pump to prevent the internal pipes from freezing, which is a normal protective feature during very cold weather.

Low Engineer only
S.39

Your boiler has detected that an external safety switch for your underfloor heating system is currently open, preventing the heating from turning on.

Medium Engineer only £100-250

Parts commonly replaced

  • Underfloor heating thermal cut-out switch
  • External wiring loom
  • System controller

Related codes

Showing 61–70 of 71
S.42

Your boiler has detected that a safety flap in the exhaust pipe is stuck in the closed position, which prevents the unit from venting fumes safely and stops it from starting up.

High Engineer only £120-250

Parts commonly replaced

  • Flue non-return flap mechanism
  • Flue sensor
  • Fan assembly

Related codes

S.53

Your boiler has temporarily paused because it has detected a lack of water or poor flow through the system.

High Engineer only £100-£250

Parts commonly replaced

  • Water pressure sensor
  • Circulating pump
  • Automatic bypass valve

Related codes

S.54

Your boiler has temporarily paused because the water pressure is too low or the water isn't circulating properly between the pipes.

High DIY-safe

What to check first

  1. Check the pressure gauge on the front of your boiler to see if it has dropped below 1 bar.
  2. Use the filling loop underneath your boiler to top up the system pressure until it reaches between 1 and 1.5 bars.
  3. Reset the boiler using the reset button if it does not restart automatically.

Parts commonly replaced

  • Water pressure sensor
  • Circulating pump
  • Automatic air vent

Related codes

S.88

Your boiler is currently running an automatic air-clearing cycle to remove trapped air from the system, which is a normal process after recent maintenance or a pressure drop.

Low Engineer only
S.91

Your boiler is currently set to a special demonstration mode used for showroom displays, which prevents it from heating your home or water normally.

High Engineer only £80-120
S.96

Your boiler is currently performing a self-check of its internal sensors and has temporarily paused heating and hot water to ensure everything is operating safely.

Medium Engineer only £120-250

Parts commonly replaced

  • Return NTC thermistor
  • Wiring harness

Related codes

S.98

Your boiler is currently running a self-check process, which is temporarily pausing your heating and hot water to ensure everything is working correctly.

Low Engineer only £100-200

Parts commonly replaced

  • Return temperature sensor
  • Wiring harness
  • Main PCB

Related codes

Showing 71–71 of 71
S.109

Your boiler is currently in a temporary standby state and is not actively heating, often because the system has been switched off at the controls or is waiting for a signal from your thermostat.

Low DIY-safe

What to check first

  1. Check your room thermostat or smart controller to ensure it is calling for heat
  2. Ensure the boiler's on/off switch on the front panel is set to the 'on' position
  3. Check that your heating timer or programmer is currently set to an 'on' period