Chaffoteaux Minima HE System 30 Fault codes & diagnostics

34 fault codes with plain-English explanations, severity ratings, DIY guidance, and repair cost estimates.

System Natural Gas 30 kW Discontinued
GC Number 41-980-34
Download the Chaffoteaux Minima HE System 30 manual The official installation & service manual (PDF) — the exact document these fault codes were verified against. PDF

The fault code is already on your display

Note it down before pressing reset — resetting clears the code immediately. How to read fault codes →

Severity at a glance

Each cell = one fault code. Hover to identify.
2 Emergency 22 High 7 Medium 3 Low

All 34 documented codes

Tap any card for details

A 01

Your boiler has detected that it is running too hot and has automatically shut itself down to prevent damage.

High Engineer only £120-250 Community-sourced, unverified

Parts commonly replaced

  • NTC sensor
  • Circulation pump
  • Heat exchanger

Related codes

A 03

Your boiler is trying to start but cannot detect a flame, so it has safely shut itself down to prevent gas from building up.

High Engineer only £120-250 Community-sourced, unverified

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • PCB

Related codes

A 36

Your boiler has detected that the gases leaving the exhaust flue are much hotter than they should be, causing the system to shut down for safety.

Emergency Engineer only £150-350 Community-sourced, unverified

Parts commonly replaced

  • Primary heat exchanger
  • NTC flue sensor
  • Overheat thermostat

Related codes

A 37

Your boiler's internal computer has encountered a critical error and can no longer process instructions, meaning the unit cannot operate.

High Engineer only £250-450 Community-sourced, unverified

Parts commonly replaced

  • Main PCB (Printed Circuit Board)

Related codes

A 39

Your boiler has detected an internal electronic error within its main control brain, preventing it from operating safely.

High Engineer only £250-450 Community-sourced, unverified

Parts commonly replaced

  • Main PCB

Related codes

A 40

Your boiler's internal computer is experiencing a communication error, meaning it has safely shut down to prevent incorrect operation.

High Engineer only £250-450 Community-sourced, unverified

Parts commonly replaced

  • Main Control PCB
  • Wiring harness

Related codes

A 41

Your boiler is struggling to clear exhaust gases safely, so it has stopped working to prevent any risk of fumes entering your home.

High Engineer only £150-300 Community-sourced, unverified

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Wiring harness

Related codes

E 02

Your boiler has stopped working because it cannot move the water around the system effectively.

High DIY-safe £120-250 Community-sourced, unverified

What to check first

  1. Check your boiler pressure gauge; if it is below 1 bar, use the filling loop to top it up to 1.5 bar.
  2. Check if your central heating system is full of air by bleeding your radiators.
  3. Ensure all radiator valves are fully open to allow water to flow freely.

Parts commonly replaced

  • Central heating pump
  • Pressure sensor
  • Flow switch

Related codes

E 04

Your boiler is failing to light the internal flame needed to produce heat and hot water, so it has shut down as a safety precaution.

High Engineer only £150-300 Community-sourced, unverified

Parts commonly replaced

  • Ignition electrode
  • Ionisation probe
  • Gas valve
  • PCB

Related codes

E 05

Your boiler has detected that the water temperature is very low and has automatically switched on its internal pump to circulate water and prevent the pipes from freezing.

Low Engineer only Community-sourced, unverified

Parts commonly replaced

  • NTC temperature sensor
  • Main PCB

Related codes

Showing 11–20 of 34
E 06

Your boiler has detected that the internal pipes are at risk of freezing and has temporarily locked out to prevent damage.

Medium Engineer only £120-250 Community-sourced, unverified

Parts commonly replaced

  • NTC temperature sensor
  • Main PCB
  • Pump

Related codes

E 07

Your boiler has detected that water is not moving through the system properly, which is preventing it from heating your home safely.

High Engineer only £150-300 Community-sourced, unverified

Parts commonly replaced

  • Central heating pump
  • Flow sensor
  • System filter

Related codes

E 08

Your boiler has detected that the water level inside the heating system is too low to operate safely.

High DIY-safe £80-150 Community-sourced, unverified

What to check first

  1. Locate the external filling loop, which is a silver braided hose connected to two valves under the boiler.
  2. Slowly open both valves to allow mains water to enter the system until the pressure gauge on the boiler reads between 1.0 and 1.5 bar.
  3. Close both valves tightly and check for any leaks around the filling loop connections.

Parts commonly replaced

  • Pressure gauge
  • Pressure relief valve
  • Filling loop

Related codes

E 11

Your boiler has lost the ability to detect that water is flowing through its internal pipes, which prevents it from firing up to heat your home or water.

High Engineer only £150-250 Community-sourced, unverified

Parts commonly replaced

  • Flow sensor
  • Wiring harness
  • PCB

Related codes

E 12

Your boiler is currently unable to detect if water is moving through the system correctly, which has caused it to stop heating to prevent internal damage.

High Engineer only £150-250 Community-sourced, unverified

Parts commonly replaced

  • Flow sensor
  • Wiring harness

Related codes

E 13

Your boiler has lost its connection to the temperature sensor that monitors the water returning to the system, meaning it can no longer accurately read how hot or cold the water is.

High Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Return NTC thermistor sensor
  • Wiring harness

Related codes

E 14

Your boiler has stopped working because it cannot correctly read the temperature of the water returning to it, as a sensor or its wiring is faulty.

High Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Return NTC sensor
  • Wiring harness

Related codes

E 15

Your boiler is struggling to detect the outside temperature because the cable connected to the outdoor weather sensor is either loose or broken.

Low Engineer only £120-180 Community-sourced, unverified

Parts commonly replaced

  • Outdoor temperature sensor
  • Sensor wiring

Related codes

E 16

Your boiler is receiving an incorrect signal from an optional temperature probe located outside your home, which may cause your heating to run less efficiently.

Low Engineer only £120-200 Community-sourced, unverified

Parts commonly replaced

  • Outdoor temperature sensor
  • Wiring harness

Related codes

E 18

Your boiler is struggling to keep the burner flame stable, causing it to detach from the burner surface, which forces the system to shut down for safety.

High Engineer only £150-300 Community-sourced, unverified

Parts commonly replaced

  • Gas valve
  • Burner assembly
  • Air pressure switch
  • Venturi

Related codes

Showing 21–30 of 34
E 20

Your boiler has detected a flame even though it is telling the gas supply to stay off, which is a safety fault that prevents the system from running.

Emergency Engineer only £150-250 Community-sourced, unverified

Parts commonly replaced

  • Gas valve
  • Main PCB
  • Flame rectification probe

Related codes

E 22

Your boiler has detected an issue with its internal airflow system, which is preventing it from firing up safely.

High Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Air pressure switch
  • Venturi
  • Fan assembly

Related codes

E 23

Your boiler has detected that the internal fan is spinning too slowly, which means it cannot safely clear waste gases and has shut down to prevent a hazard.

High Engineer only £180-350 Community-sourced, unverified

Parts commonly replaced

  • Fan assembly
  • PCB
  • Wiring harness

Related codes

E 25

Your boiler is struggling to read the temperature of your hot water cylinder, which means it cannot safely heat your water.

High Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Hot water cylinder sensor
  • Wiring harness

Related codes

E 26

Your boiler is struggling to read the temperature of your hot water cylinder because a sensor has developed an electrical fault.

Medium Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • DHW Tank Sensor
  • Wiring Harness

Related codes

E 27

Your boiler has detected an issue with the sensor responsible for monitoring your hot water cylinder, which means it cannot accurately determine if your water is at the correct temperature.

Medium Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Cylinder NTC sensor
  • Wiring harness

Related codes

E 29

Your boiler has lost its connection to the thermostat that measures the temperature in your home, so it doesn't know when to turn the heating on or off.

Medium Engineer only £120-200 Community-sourced, unverified

Parts commonly replaced

  • Room thermostat
  • External wiring loom
  • PCB

Related codes

E 30

Your boiler is struggling to detect the room temperature correctly because of a wiring or connection error, which is preventing your heating from operating reliably.

Medium Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Room thermostat
  • External sensor wiring
  • PCB

Related codes

E 33

Your boiler has detected that a safety sensor connected to your underfloor heating system is not sending a signal, which is preventing the system from operating correctly.

Medium Engineer only £120-250 Community-sourced, unverified

Parts commonly replaced

  • External thermostat
  • Wiring harness
  • PCB

Related codes

E 34

Your boiler has detected a disconnection in the sensor that monitors the air and gases flowing through your flue system, which prevents it from operating safely.

High Engineer only £150-250 Community-sourced, unverified

Parts commonly replaced

  • Flue sensor
  • Wiring harness

Related codes

Showing 31–34 of 34
E 35

Your boiler has detected a faulty connection in the system that monitors the safe exit of exhaust gases, so it has shut down to ensure your home remains safe.

High Engineer only £120-220 Community-sourced, unverified

Parts commonly replaced

  • Flue sensor
  • Wiring harness

Related codes

E 36

Your boiler has detected that the exhaust gases leaving the flue are hotter than they should be, causing it to shut down for safety.

High Engineer only £150-300 Community-sourced, unverified

Parts commonly replaced

  • Flue gas sensor
  • Primary heat exchanger
  • Pump

Related codes

E 37

Your boiler has lost the ability to send signals between its internal components, which means it has stopped working as a safety precaution.

High Engineer only £200-450 Community-sourced, unverified

Parts commonly replaced

  • Main PCB
  • Wiring harness

Related codes

E 38

Your boiler has been locked out because the reset button has been pressed too many times in a short period, and it now needs to be left alone to reset its internal memory.

Medium DIY-safe Community-sourced, unverified

What to check first

  1. Switch the boiler off at the fused spur or mains isolation switch
  2. Wait for at least 15 to 20 minutes to allow the electronic lockout timer to clear
  3. Switch the power back on and see if the boiler resumes normal operation

Related codes