Navien NCB CE Fault codes & diagnostics

94 fault codes with plain-English explanations, severity ratings, DIY guidance, and repair cost estimates.

Combi Natural GasLPG 24-40 kW 2014-present
Download the Navien NCB CE manualThe official installation and service manual (PDF), the document these fault codes were read from. PDF

The fault code is already on your display

Note it down before pressing reset — resetting clears the code immediately. How to read fault codes →

Severity at a glance

Each cell = one fault code. Hover to identify.
13 Emergency 73 High 5 Medium 3 Low

All 94 documented codes

Tap any card for details

001

Your boiler has detected an internal issue where the fan is not spinning at the required speed to safely exhaust gases.

High Engineer only £150-300

Parts commonly replaced

  • Fan assembly
  • Wiring harness
  • PCB

Related codes

003

Your boiler has failed to ignite because it was unable to sense a flame after starting up.

High Engineer only £120-250

Parts commonly replaced

  • Ignition electrode
  • Flame sensor
  • Gas valve

Related codes

004

Your boiler has detected a failure to ignite the flame, meaning it is currently unable to provide heating or hot water.

High Engineer only £120-£250

Parts commonly replaced

  • Ignition electrode
  • Flame rod sensor
  • Gas valve

Related codes

012

Your boiler has detected that it is not receiving enough water flow to operate safely and has shut itself down to prevent damage.

High Engineer only £120-250

Parts commonly replaced

  • Flow sensor
  • Circulation pump
  • Primary heat exchanger

Related codes

012E

Your boiler has detected that the flame inside has unexpectedly gone out, so it has safely shut down to stop any unburned gas from building up.

High Engineer only £100-250

Parts commonly replaced

  • Flame sensor
  • Gas valve
  • Ignition lead

Related codes

016

Your boiler has detected that it is overheating and has shut itself down to prevent any damage to the internal parts.

High Engineer only £120-250

Parts commonly replaced

  • Pump
  • Heat exchanger
  • Temperature sensor

Related codes

016E

Your boiler has temporarily shut down because an internal safety switch detected that the water inside has gotten too hot.

High Engineer only £100-£250

Parts commonly replaced

  • High limit thermostat
  • Bi-metal thermal switch
  • Circulator pump

Related codes

030

Your boiler has failed to detect a flame, meaning it cannot ignite to provide you with heating or hot water.

High Engineer only £120-250

Parts commonly replaced

  • Ignition electrode
  • Flame sensor
  • Gas valve
046

Your boiler has detected an issue with the water pressure sensor, which is preventing it from operating correctly.

High Engineer only £150-250

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

047

Your boiler has detected an issue with the airflow management system, meaning it cannot operate safely and has shut itself down to prevent damage.

High Engineer only £150-300

Parts commonly replaced

  • Air pressure switch
  • Fan assembly
  • Ventilation flue assembly

Related codes

Showing 11–20 of 94
060

Your boiler has detected an issue with the air supply or exhaust system, meaning it cannot safely vent the gases produced during combustion.

Emergency Engineer only £150-300

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Flue assembly

Related codes

109

Your boiler has detected an issue with the air pressure inside the unit, meaning it cannot safely vent the exhaust gases.

Emergency Engineer only £150-350

Parts commonly replaced

  • Air pressure sensor
  • Venturi
  • Fan assembly
110

Your boiler is failing to light the flame properly, which means it cannot produce heating or hot water until the ignition system is checked.

High Engineer only £120-250

Parts commonly replaced

  • Ignition electrode
  • Flame sensor
  • Gas valve
110E

Your boiler is struggling to breathe properly because the pipework that lets air in and smoke out is likely blocked, frozen, or damaged.

Emergency Engineer only £120-250

Parts commonly replaced

  • Flue terminal
  • Condensate trap
  • Fan assembly
  • Air pressure switch

Related codes

205

Your boiler has detected an issue with the air intake or exhaust system, meaning it cannot safely vent gases and has shut down to protect your home.

Emergency Engineer only £150-£300

Parts commonly replaced

  • Air pressure switch
  • Fan assembly
  • Flue seals
218

Your boiler has detected an issue with the water flow or pressure sensor, meaning it cannot accurately tell if water is moving through the system to heat it safely.

High Engineer only £150-250

Parts commonly replaced

  • Flow sensor
  • Pressure sensor
  • Wiring harness
302

Your boiler has detected an issue with the air supply or exhaust system, which prevents it from operating safely.

Emergency Engineer only £150-300

Parts commonly replaced

  • Air pressure switch
  • Fan assembly
  • Flue seals
352

Your boiler is failing to detect the necessary internal pressure or airflow, causing the system to lock out for safety.

High Engineer only £150-300

Parts commonly replaced

  • Air pressure switch
  • Fan assembly
  • Main PCB

Related codes

353

Your boiler has detected an issue with the flame and has safely shut itself down to prevent any unsafe operation.

High Engineer only £150-300

Parts commonly replaced

  • Flame rod
  • Ignition electrode
  • Gas valve

Related codes

407

Your boiler has detected an issue with the sensor used to monitor the water pump, preventing the system from circulating water correctly.

High Engineer only £180-350

Parts commonly replaced

  • Circulation pump
  • Pump wiring harness
  • Main PCB
Showing 21–30 of 94
421

Your boiler has detected a problem with the internal flow sensor, which means it cannot accurately measure the movement of water to heat your home.

High Engineer only £180-300

Parts commonly replaced

  • Flow Sensor
  • Flow Switch
  • Wiring Harness

Related codes

515

Your boiler has detected an internal communication error with its main control unit, causing it to shut down for safety.

High Engineer only £180-350

Parts commonly replaced

  • Main Control PCB
  • Communication wiring harness

Related codes

517

Your boiler has detected an internal communication failure between its main control boards, which prevents it from operating safely.

High Engineer only £180-350

Parts commonly replaced

  • Main Control Board
  • Communication Wiring Harness
594

Your boiler has detected an issue with the internal air or exhaust system that prevents it from firing up safely.

High Engineer only £150-300

Parts commonly replaced

  • Air pressure switch
  • Fan assembly
  • Flue sensor
615

Your boiler has detected an internal communication error between its main control boards, which prevents it from operating correctly.

High Engineer only £150-300

Parts commonly replaced

  • Main control board
  • Communication wiring harness
740

Your boiler is struggling to communicate with its internal control system, which has caused it to shut down for safety reasons.

High Engineer only £150-300

Parts commonly replaced

  • Main PCB
  • Wiring harness

Related codes

782

Your boiler has lost communication with the internal 3-way valve, meaning it cannot correctly switch between heating your radiators and providing hot water.

High Engineer only £150-250

Parts commonly replaced

  • 3-way diverter valve
  • Diverter valve motor
  • Wiring harness
E.782

Your boiler's main control panel is having trouble talking to the internal computer, which has caused the system to stop working.

High Engineer only £150-300

Parts commonly replaced

  • Main PCB
  • Wiring harness
  • Display interface module
E001

Your boiler has detected that its internal water temperature has become dangerously high and has shut itself down to prevent damage.

High Engineer only £150-350

Parts commonly replaced

  • Central heating pump
  • Flow sensor
  • Heat exchanger
  • Diverter valve

Related codes

E003

Your boiler is failing to light the flame needed to produce heat and hot water.

High Engineer only £120-250

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • PCB

Related codes

Showing 31–40 of 94
E004

Your boiler is detecting a flame inside the unit even when it has been told to turn off, which triggers a safety shutdown to prevent gas build-up.

Emergency Engineer only £150-300

Parts commonly replaced

  • Flame rectification electrode
  • Gas valve
  • PCB (Main control board)

Related codes

E012

Your boiler is failing to light the internal flame needed to produce heat and hot water safely.

High Engineer only £150-300

Parts commonly replaced

  • Flame rod sensor
  • Ignition lead
  • Gas valve
E016

Your boiler has detected that it is getting dangerously hot and has shut itself down to prevent damage or fire risk.

Emergency Engineer only £150-300

Parts commonly replaced

  • High limit sensor
  • Central heating pump
  • Heat exchanger
E030

Your boiler is detecting an issue with water flow or heat levels, which could mean dangerous air or gas is trapped inside where it shouldn't be.

Emergency Engineer only £150-400

Parts commonly replaced

  • Heat exchanger
  • Circulation pump
  • Flow sensor

Related codes

E046

Your boiler is struggling to read its internal temperature correctly, which is preventing it from safely heating your home's water.

High Engineer only £150-250

Parts commonly replaced

  • Temperature sensor (thermistor)
  • Wiring harness

Related codes

E047

Your boiler is struggling to accurately measure its internal water temperature, so it has stopped working as a safety precaution.

High Engineer only £150-250

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring Harness

Related codes

E047-1

Your boiler has temporarily stopped working because it has detected an issue with the temperature sensor on its exhaust flue.

High Engineer only £100-200

Parts commonly replaced

  • Exhaust thermistor
  • Flue temperature sensor harness

Related codes

E047-2

Your boiler has detected an electrical fault with the temperature sensor on the exhaust flue, causing it to shut down for safety.

High Engineer only £150-250

Parts commonly replaced

  • Exhaust thermistor
  • Flue temperature sensor
  • Wiring harness

Related codes

E060

Your boiler is having trouble controlling the air and gas balance required for safe combustion, so it has safely shut itself down to prevent any issues.

High Engineer only £150-350

Parts commonly replaced

  • Venturi assembly
  • Gas valve
  • Fan assembly
  • PCB
E060-1

Your boiler has detected an issue with its internal airflow and safety sensors, which temporarily stops it from operating to keep your home safe.

High Engineer only £150-300

Parts commonly replaced

  • Venturi limit switch
  • Air pressure switch
  • Wiring harness

Related codes

Showing 41–50 of 94
E060-2

Your boiler has detected an issue with the internal air flow safety switch, which stops the boiler from operating if it is stuck in the closed position.

High Engineer only £150-300

Parts commonly replaced

  • Venturi limit switch
  • Air pressure switch
  • Wiring harness

Related codes

E060-3

Your boiler has detected an issue with the internal airflow safety switch, which stops the boiler from running to ensure dangerous gases cannot build up.

Emergency Engineer only £150-300

Parts commonly replaced

  • Venturi limit switch
  • Air pressure switch
  • Wiring harness

Related codes

E109

Your boiler has stopped working because the internal fan which clears waste gases isn't spinning, meaning it has safely shut down to prevent any risk.

High Engineer only £180-350

Parts commonly replaced

  • Fan assembly
  • Wiring harness
  • PCB

Related codes

E109-0

Your boiler has detected an issue with the internal fan that safely clears combustion gases, so it has locked out to keep your home safe.

High Engineer only £150-350

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Printed Circuit Board (PCB)

Related codes

E110

Your boiler is struggling to breathe because it cannot effectively move air through the system, meaning it has shut down for safety.

High Engineer only £180-350

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Flue seals
E110-1

Your boiler has detected a blockage in the exhaust flue or a problem with the internal fan, which stops it from safely clearing waste gases outside.

Emergency Engineer only £150-350

Parts commonly replaced

  • Flue assembly
  • Flue terminal
  • Boiler fan
  • Air pressure switch

Related codes

E110-2

Your boiler has temporarily stopped working because it has detected a blockage in the exhaust flue that removes waste gases outside.

Emergency Engineer only £100-250

Parts commonly replaced

  • Flue terminal
  • Air pressure switch
  • Exhaust fan

Related codes

E110-3

Your boiler has detected a blockage in the exhaust flue that removes waste gases outside, so it has safely shut down to prevent harmful fumes from building up in your home.

Emergency Engineer only £90-180

Parts commonly replaced

  • Flue terminal
  • Exhaust fan
  • Pressure switch tube

Related codes

E127

Your boiler's air pressure sensor is failing to detect the correct airflow, meaning the unit has shut down to ensure safe operation.

High Engineer only £150-300

Parts commonly replaced

  • Air Pressure Sensor
  • Flue assembly
  • Fan
E205

Your boiler's temperature sensors are providing conflicting or faulty data, so it has safely shut itself down to prevent overheating.

High Engineer only £150-250

Parts commonly replaced

  • DHW thermistor
  • Central heating thermistor
  • Wiring harness
Showing 51–60 of 94
E205-1

Your boiler has detected an issue with the sensor that measures the temperature of the water leaving for your radiators, causing it to stop heating safely.

High Engineer only £150-£250

Parts commonly replaced

  • Heating supply thermistor
  • Wiring harness

Related codes

E205-2

Your boiler has temporarily stopped working because a temperature sensor measuring the heating water has registered a fault.

High Engineer only £100-£200

Parts commonly replaced

  • Central heating thermistor
  • Wiring harness

Related codes

E218

Your boiler's temperature sensor is providing faulty readings, causing the system to stop operating to prevent potential overheating.

High Engineer only £150-250

Parts commonly replaced

  • NTC Thermistor
  • Wiring harness
E218-1

Your boiler has temporarily stopped working because it cannot properly read the temperature of the water returning from your radiators.

High Engineer only £100-£200

Parts commonly replaced

  • Return thermistor
  • Wiring harness

Related codes

E218-2

Your boiler has temporarily stopped working because it has detected an issue with the sensor that measures the temperature of the water returning from your radiators.

High Engineer only £100-£200

Parts commonly replaced

  • Return thermistor
  • Wiring harness

Related codes

E302

Your boiler has stopped working because the water pressure inside the system has dropped too low to operate safely.

High DIY-safe £80-150

What to check first

  1. Locate the external filling loop, which is a flexible braided hose usually found underneath the boiler
  2. Open the valves at both ends of the filling loop to let mains water into the system
  3. Monitor the pressure gauge on the front of the boiler until the needle reaches between 1.0 and 1.5 bar
  4. Close both valves tightly and remove the filling loop if required by your specific model

Parts commonly replaced

  • Filling loop
  • Pressure relief valve
  • Pressure sensor
E302-0

Your boiler has temporarily stopped working because the water pressure inside the system has dropped too low.

High DIY-safe

What to check first

  1. Locate the filling loop valves underneath your boiler or near the pipework.
  2. Open the valves slowly to let mains water into the system while watching the pressure gauge on the front panel.
  3. Stop filling once the needle reaches between 1.0 and 1.5 bar, then close the valves tightly.

Parts commonly replaced

  • Pressure relief valve
  • Pressure sensor
  • Auto air vent

Related codes

E351

Your boiler is struggling to understand how much water is inside it, so it has stopped working to prevent any potential damage.

High Engineer only £150-250

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

E352

Your boiler is currently unable to read its own internal water pressure, which prevents it from operating safely to provide heat or hot water.

High Engineer only £150-250

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

E352-0

Your boiler has automatically stopped working because the water pressure inside the system has risen higher than it should be.

Emergency DIY-safe £90-180

What to check first

  1. Locate the filling loop valves connected to your boiler.
  2. Ensure both valves are fully closed and not letting extra water into the system.
  3. Bleed one or two radiators in your home to release excess water and bring the pressure gauge down to between 1 and 1.5 bar.

Parts commonly replaced

  • Pressure Relief Valve
  • Filling Loop
  • Expansion Vessel

Related codes

Showing 61–70 of 94
E353

Your boiler has detected an issue with how it manages water flow and pressure, which means it cannot safely produce hot water for your taps or home.

High Engineer only £180-350

Parts commonly replaced

  • Water pressure sensor
  • DHW heat exchanger
  • Diverter valve

Related codes

E353-1

Your boiler has temporarily stopped working because it cannot properly read the water pressure inside the system.

High Engineer only £100-200

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

E353-2

Your boiler is temporarily locked out because it is getting an incorrect electronic signal from its internal water pressure monitoring system.

Medium Engineer only £120-250

Parts commonly replaced

  • Water Pressure Sensor
  • Wiring Harness
  • Main Printed Circuit Board (PCB)

Related codes

E407

Your boiler is struggling to accurately read its internal temperature, so it has safely shut down to prevent overheating.

High Engineer only £150-250

Parts commonly replaced

  • NTC Thermistor
  • Wiring harness
E407-1

Your boiler is not able to accurately read the temperature of your hot water because a sensor is disconnected or faulty, which stops it from working properly.

High Engineer only £100-200

Parts commonly replaced

  • Hot water thermistor
  • Wiring harness

Related codes

E407-2

Your boiler is temporarily unable to accurately measure your hot water temperature due to a faulty internal sensor.

Medium Engineer only £90-180

Parts commonly replaced

  • Hot water NTC thermistor
  • Wiring harness

Related codes

E421

Your boiler is struggling to read its internal water temperature correctly, so it has shut down to prevent overheating or system damage.

High Engineer only £150-250

Parts commonly replaced

  • Flow Thermistor
  • Return Thermistor
  • Wiring Harness

Related codes

E421-1

Your boiler is temporarily unable to accurately measure the temperature of the incoming cold water, which may affect its ability to provide stable hot water.

Medium Engineer only £100-£200

Parts commonly replaced

  • Cold water inlet thermistor
  • Wiring harness

Related codes

E421-2

Your boiler is temporarily unable to accurately measure the temperature of the incoming cold water, which usually prevents it from heating water properly.

High Engineer only £120-250

Parts commonly replaced

  • Cold water inlet thermistor
  • Wiring harness

Related codes

E439

Your boiler is struggling to detect the movement of water, which means it cannot safely start heating your home or providing hot water.

High Engineer only £150-250

Parts commonly replaced

  • Flow sensor
  • Water turbine assembly
  • Wiring harness
Showing 71–80 of 94
E515

Your boiler's main control computer is experiencing an internal electronic fault, preventing the system from operating correctly.

High Engineer only £250-450

Parts commonly replaced

  • Main PCB
  • Wiring harness
E515-1-7

Your boiler's main control unit has temporarily lost the ability to 'talk' to its internal parts, meaning it has safely shut down to prevent unexpected behaviour.

High Engineer only £200-450

Parts commonly replaced

  • Main PCB
  • Wiring harness

Related codes

E515-8

Your boiler has lost its connection to the part responsible for creating the spark, meaning it cannot safely ignite to provide you with heating and hot water.

High Engineer only £150-£350

Parts commonly replaced

  • Igniter
  • Main Control PCB

Related codes

E515-9

Your boiler has lost the connection between its main electronic brain and the internal fan that safely pushes out gases.

High Engineer only £150-300

Parts commonly replaced

  • Fan assembly
  • Wiring harness
  • Main PCB

Related codes

E515-10

Your boiler's main electronic control unit has detected an internal monitoring or communication error, so it has safely shut down to prevent unexpected operation.

High Engineer only £200-450

Parts commonly replaced

  • Printed Circuit Board (PCB)
  • Wiring harness

Related codes

E515-11-12

Your boiler has temporarily stopped working because the main control board has lost communication with its internal air and gas monitoring system.

High Engineer only £150-350

Parts commonly replaced

  • Main PCB
  • Venturi Assembly
  • Wiring Harness

Related codes

E515-13-14

Your boiler's main control board has lost communication with the valve that directs hot water between your taps and your radiators.

High Engineer only £150-300

Parts commonly replaced

  • 3-Way Valve
  • Main PCB
  • Wiring Harness

Related codes

E517

Your boiler's internal configuration settings are currently mismatched or incorrect, preventing the system from running properly.

High Engineer only £120-200

Parts commonly replaced

  • Main PCB
E517-0

Your boiler has detected an internal configuration error with its control board settings, meaning it cannot operate safely until corrected.

High Engineer only £90-180

Parts commonly replaced

  • Main Control Board
  • PCB

Related codes

E594

Your boiler's internal electronic systems are having trouble talking to each other, which means the device has stopped working to prevent further faults.

High Engineer only £250-450

Parts commonly replaced

  • Main PCB
  • Communication wiring harness
Showing 81–90 of 94
E594-0

Your boiler has encountered an internal memory storage error, meaning it has lost its configuration settings and needs to be reset or repaired by a professional.

High Engineer only £150-350

Parts commonly replaced

  • PCB (Printed Circuit Board)
  • Control Panel

Related codes

E615

Your boiler's main computer control panel is failing to process instructions correctly, which has caused the system to stop operating for safety reasons.

High Engineer only £250-450

Parts commonly replaced

  • Main PCB
  • Wiring harness
E615-0

Your boiler has detected a communication or safety data error regarding the temperature inside the main heat exchanger and has shut down to protect itself.

High Engineer only £150-350

Parts commonly replaced

  • High limit switch
  • Primary heat exchanger sensor
  • Main PCB

Related codes

E615-1

Your boiler has temporarily stopped working because it cannot properly read the temperature of the exhaust gases coming out of the flue.

Medium Engineer only £100-£250

Parts commonly replaced

  • Flue gas temperature sensor
  • Wiring harness
  • Main control PCB

Related codes

E615-2

Your boiler has detected an issue with the sensor that monitors the burner flame, so it has safely locked out to prevent unsafe operation.

High Engineer only £150-£300

Parts commonly replaced

  • Flame sensor electrode
  • Main PCB

Related codes

E615-3-14

Your boiler's main control unit has experienced an internal memory error, meaning it has lost its stored settings and cannot operate safely.

High Engineer only £250-450

Parts commonly replaced

  • Printed Circuit Board (PCB)

Related codes

E615-15-16

Your boiler has detected an incorrect reading from its internal water pressure sensor, which means it cannot safely verify the system pressure.

High Engineer only £120-250

Parts commonly replaced

  • Water pressure sensor
  • Wiring harness

Related codes

E740

Your boiler has lost the connection to the thermometer installed outside your home, so it cannot automatically adjust your heating based on the current weather.

Low Engineer only £120-180

Parts commonly replaced

  • Outdoor temperature sensor
  • Wiring harness
E740-1

Your boiler has lost connection to the weather sensor outside, meaning it can no longer automatically adjust your heating temperature based on the weather.

Low Engineer only £90-180

Parts commonly replaced

  • Outdoor temperature sensor
  • Sensor wiring

Related codes

E740-2

Your boiler is receiving an incorrect signal from the optional outdoor weather sensor because of a wiring short, though your heating and hot water will still work.

Low Engineer only £90-180

Parts commonly replaced

  • Outdoor temperature sensor
  • External sensor wiring

Related codes

Showing 91–94 of 94
E782

Your boiler's internal electronic control boards are failing to talk to each other, which means the system cannot safely manage your heating or hot water.

High Engineer only £200-450

Parts commonly replaced

  • Main control board (PCB)
  • Communication wiring harness
E782-0

Your boiler's main control panel has temporarily lost its connection, meaning it cannot talk to the internal parts needed to run your heating and hot water.

High Engineer only £150-300

Parts commonly replaced

  • Wiring harness
  • Main PCB
  • Display control board

Related codes

E783

Your boiler is having trouble communicating with your wall-mounted thermostat or remote control panel, meaning it may not know when to turn on or off.

Medium Engineer only £120-250

Parts commonly replaced

  • OpenTherm interface cable
  • PCB control board
  • Remote thermostat unit

Related codes

E787

Your boiler's computer is having trouble restarting correctly after a software or power glitch, preventing it from functioning properly.

High Engineer only £120-250

Parts commonly replaced

  • Main PCB
  • Control wiring harness

Related codes

1 operating states & engineer diagnostics

Not faults — these are normal operating states. Tap to expand.

Avoid the next call-out bill

Monthly cover means no unexpected bills when your boiler breaks down.

Approved partner
Domestic Appliance Guard
Unlimited call-outs, 24/7 helpline, no price-hike promise
Get a quote →

Affiliate links. We may earn a commission at no extra cost to you.