What the manual says
Manufacturer manualFault EE (shown when ignition, gas train opening or ionisation current build-up fails). Ignition: Check ignition module (control voltage 230 V across plugs "X2.1" and "X2.2"). Check the gas supply. Gas train opens: Check the gas train (control voltage 230 V~); check the gas supply pressure. Ionisation current builds: Check setting of ionisation electrode. Purge the gas line.
Engineer required
This is a high severity fault. Stop using the boiler and call a Gas Safe registered engineer. Do not attempt gas-related repairs yourself.